4.91xx.00.061 Clima Sensor D

The Clima Sensor D serves for the measurement of environmental dataModels are available to measure:• Wind speed• Precipitation• Brigthness• Twilight• Air Temperature• rel. Humidity These are avai

  • Product Name:Clima Sensor D
  • Model:4.91xx.00.061
  • Maunufactor:Thies Clima
  • Country:DE

The Clima Sensor D serves for the measurement of environmental data

Models are available to measure:
• Wind speed
• Precipitation
• Brigthness
• Twilight
• Air Temperature
• rel. Humidity
 
These are available as
• Serial RS 485/­422
telegram and as
• Analogue outputs
for further processing
The CLIMA Sensor D has an internal DCF77 receiver, which takes the time signal of an atomic clock, and integrates it into the data telegram.
Ranges of application are:
• Building control systems
• Control technique
• Green house technique
• Processing of the acquired
data to recording or display instruments.
Depending on the model, the following data can be measured by the Clima Sensor D:
• Wind velocity
• Precipitation (yes/­no)
• Brightness in Eastern, Southern and Western direction
• Twilight
• Temperature
• Rel. humidity
The respective holder serves for the mounting at masts or plane surfaces, depending on the range of application. Instrument with internal condensation shield

Precipitation
Measuring range generalyes /­ no
Switch-off-delayapprox. 2 min
Sensitivityfine drizzle
Brightness
Measuring range0 ... 150 kLux
Spectral range700 ... 1050 nm
Accuracy±10 % vom rel. Messwert
Measured directionsSouth, East, West
Twilight
Measuring range0 ... 250 Lux
Spectrum range700 ... 1050 nm
Accuracy±10 % of meas. value
Data output digital
InterfaceRS485 /­ RS422
Baudrate1200 ... 19200 Baud
Duplex modeFull /­ halfduplex
ProtocolASCII
Parameterenvironmental data,
housing temperature,
date /­ time,
sensor status,
checksum
Data output analog
Typemax. 8 x 0 ... 10V
( incl. Precipitation: 0 or 10 V )
Voltage outputmin. 10 kê
General
Power supply16 ... 28V DC or
16 ... 24 V AC, max. 150 mA
Current consumpt.600 mA
Electr. connection10 m cable,
LiYCY 16 x 0.14 mm²,
UV - resistant
MountingWall or mast mounting,
retaining clamb,
stainless steel