ONSET HOBO UX90-001 State Data Logger

OverviewThe HOBO State/Pulse/Event/Runtime data logger records state changes,electronic pulses and mechanical or electrical contact closures from external sensing devices. This data logger is ideal fo

  • Product Name:ONSET HOBO UX90-001 State Data Logger
  • Model:UX90-001
  • Maunufactor:Onset
  • Country:USA

Overview

The HOBO State/Pulse/Event/Runtime data logger records state changes,electronic pulses and mechanical or electrical contact closures from external sensing devices. This data logger is ideal for monitoring energy consumption, mechanical equipment operation, and water and gas flow. 

Item number UX90-001M has been discontinued.

Highlighted Features

  • One logger with 4 recording modes

  • Internal reed switch can be used to determine when a door or window is open or closed

  • Compatible with a wide range of external sensors

  • Ships with 2.5 mm input cable

  • Compatible with HOBOware and HOBOware Pro software for logger setup, graphing and analysis

In what environment does this data logger operate?

This data logger operates in an indoor environment.

What measurements does this data logger support?

The UX90-001 data logger supports the following measurements: Event, Kilowatt Hours (kWh), Motor On/Off, Pulse Input, Runtime, State Open/Closed and Water Flow


Internal Sensor

Maximum state, event, runtime frequency:      1 Hz

Preferred switch state:      No magnet present (normally open)

External Input

External contact input:      Electronic solid state switch closure or logic driven voltage output

Range:      0 to 3 V DC (USB powered), 0 to 2.5 V DC (battery powered)

Maximum pulse frequency:      50 Hz

Maximum state, event, runtime frequency:      1 Hz

Pulse, event lockout time:      0 to 1 second in 100 ms steps

Solid state switch closure:      Input Low: < 10 KΩ; Input High: > 500 KΩ

Internal weak pull-up:      100 KΩ

Input impedance:      Solid state switch closure: 100 KΩ pull up

Logger

Resolution:      Pulse: 1 pulse, Runtime: 1 second, State and Event: 1 State or Event

Logging rate:      1 second to 18 hours, 12 minutes, 15 seconds

Time accuracy:      ±1 minute per month at 25°C (77°F) (see Plot A)

Battery life:      1 year, typical with logging intervals greater than 1 minute and normally open contacts

Memory

UX90-001:      128 KB (84,650 measurements, maximum)

UX90-001M:      512 KB (346,795 measurements, maximum)

Download type:      USB 2.0 interface

Download time:      10 seconds for 128 KB; 30 seconds for 512 KB

Logger Operating Range

Logging:      -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing)

Launch/readout:      0° to 50°C (32° to 122°F) per USB specification

LCD:      LCD is visible from: 0° to 50°C (32° to 122°F); the LCD may react slowly or go blank in temperatures outside this range

Size:      3.66 x 5.94 x 1.52 cm (1.44 x 2.34 x 0.6 in.)

Weight:      23 g (0.81 oz)

Environmental rating:      IP50

The CE Marking identifies this product as complying with all relevant directives in the European Union (EU)